Features: • UniversalACinput/Fullrange • Built-in active PFC function, PF>0.95 • Protections:Short circuit/Over load/Over voltage/Over temp…
The SP-500W SP SERIES SWITCHING POWER SUPPLY WITH PFC is part of the ELEHPD S Series range. Features: • UniversalACinput/Fullrange • Built-in active PFC function, PF>0.95 • Protections:Short circuit/Over load/Over voltage/Over temperature • Forced air cooling by built-in DC fan • Built-in cooling Fan ON-OFF control • Built-in remote ON-OFF control • Built-inremotesensefunction • Fixed switching frequency at 110KHz • 2 years warranty ELEHPD manufactures and exports low voltage electrical products from Yueqing, Zhejiang, China, supplying distributors, panel builders, M&E contractors and OEM buyers worldwide.
Full catalogue description: SP SERIES SWITCHING POWER SUPPLY WITH PFC FUNCTION SP-500W
Features :
• UniversalACinput/Fullrange
• Built-in active PFC function, PF>0.95
• Protections:Short circuit/Over load/Over voltage/Over temperature
• Forced air cooling by built-in DC fan
• Built-in cooling Fan ON-OFF control
• Built-in remote ON-OFF control
• Built-inremotesensefunction
• Fixed switching frequency at 110KHz
• 2 years warranty
| Model Specification | SP-500-12 | SP-500-13.5 | SP-500-15 | SP-500-24 | SP-500-27 | SP-500-48 |
| DC output voltage | 12V | 13.5V | 15V | 24V | 27V | 48V |
| Output voltage error | ±1% | ±1% | ±1% | ±1% | ±1% | ±1% |
| Rated output current | 40A | 36A | 32A | 20A | 18A | 10A |
| Output current rage | 0-40A | 0-36A | 0-32A | 0-20A | 0-18A | 0-10A |
| Wave and noise | 240mVp-p | 240mVp-p | 240mVp-p | 240mVp-p | 200mVp-p | 300mVp-p |
| Inlet stability | ±0.5% | ±0.5% | ±0.5% | ±0.5% | ±0.5% | ±0.5% |
| Load stability(Note5) | ±1% | ±0.5% | ±0.5% | ±0.5% | ±0.5% | ±0.5% |
| DC output power | 480W | 486W | 480W | 480W | 486W | 480W |
| Efficiency | 84% | 84% | 83% | 85.5% | 86.5% | 87% |
| Adjustable range for DC voltage | 10-13.2V | 12-15V | 13.5-18V | 20-26.4V | 24-30V | 41-56V |
| AC input voltage range | 88132VAC/176264VAC BY SWITCH 4763Hz;124370VDC | |||||
| AC Input current | 7A/115V 3.5A/230V | |||||
| Power Factor | 0.95/100240VAC | |||||
| AC impulse current | 18A/115V 36A/230V | |||||
| Leakage current | <3.5mA/240VAC | |||||
| Overload protection | 105%135% TypePULSING HICCUP SHUTDOWN Reset: auto recovery | |||||
| Over-voltage protection | 13.816.2V | 15.518.2V | 1821V | 27.632.4V | 3136.5V | 57.667.2V |
| Fan control,O.T.P. | RTH1 OR RTH2>=50 FAN ON,<=45 FAN OFF,>=70 Cut off output | |||||
| Temperature coefficient | ±0.03%(050) | |||||
| Setup rise hold up time | 1.5s,50ms,20ms | |||||
| Vibration | 10500Hz,2G 10min./1cycle,Period for 60min,EACH AXES | |||||
| Withstand voltage | Input and output interval3KVAC,Input and enclosure1.5KVAC Output and enclosure0.5KVAC | |||||
| Isolation resistance | Input and output interval,Input and enclosure,Output and enclosure500VDC/100M Ohms | |||||
| Working temperature and humidity | -10+50,20%90%RH | |||||
| Store temperature and humidity | -20+85,10%95%%RH | |||||
| Overall dimension | 185*20*93mm | |||||
| Weight | 1.8Kgs | |||||
| Safety standards | UL1950,TUV EN60950 | |||||
| EMC standards | IEC1000-42,3,4,5,6,8,11 IEC100-3-2 |
A contactor is built for switching power circuits repeatedly at high current, often with motor duty ratings (AC-3) and arc-suppressing chambers. A relay switches control signals at low current. In practice: contactor for the motor, relay in the control circuit that drives the contactor coil.
Use the motor's full-load current, apply the AC-3 rating for the operating voltage, and allow for the number of starts per hour. As a rule of thumb, the contactor's AC-3 rating should be at least equal to the motor FLC, then step up one frame if the duty is heavy.
Coil voltages are specified per order. Send the model number, coil voltage and frequency you require and we will confirm availability and lead time.
Base models come with the standard auxiliary contact configuration for that frame. Add-on auxiliary blocks and mechanical interlocks can be quoted with the contactor.