800W single output high voltage switching power supply Features: · Universal AC input · Small volume, low weight, high effici…
The S series single output high voltage with PFC is part of the ELEHPD S Series range. 800W single output high voltage switching power supply Features: · Universal AC input · Small volume, low weight, high efficiency · Protections: Short circuit/over load · Indicator for power on/charge/normal(LED) · 100% full load burn-in test · Battery protection at low voltage Details ELEHPD manufactures and exports low voltage electrical products from Yueqing, Zhejiang, China, supplying distributors, panel builders, M&E contractors and OEM buyers worldwide.
Full catalogue description: S series single output high voltage with PFC function 800w switching power supply 12V 24V SMPS
| Model | SCN-800-12 | SCN-800-15 | SCN-800-24 | SCN-800-48 | |
| Output | DC Voltage | 12V | 15V | 24V | 48V |
| Voltage Tolerance | ±1% | ±1% | ±1% | ±1% | |
| Rated Current | 66A | 54A | 33A | 16.6A | |
| Current Range | 0-66A | 0-54A | 0-33A | 0-16.6A | |
| Rated Power | 800W | 800W | 800W | 800W | |
| Ripple & Noise | 150mVp-p | 150mVp-p | 240mVp-p | 480mVp-p | |
| DC Voltage Adj. Range | Can adjust from 20%~100% output voltage by external control 1-5V | ||||
| Setup,Rise,Hold Time | 800ms, 50ms, 16ms at full load | ||||
| Input | Voltage Range | 90~130VAC / 180~260 VAC 47~63 Hz; selected by switch 260~370VDC | |||
| AC Current | 13A/115 VAC 8.0A/ 230 VAC | ||||
| Efficiency | 80% | 81% | 85% | 87% | |
| Inrush Current | 60A/230V | ||||
| Leakage Current | 3.5 mA/240VAC | ||||
| Protection | Over Load | 110%~135% | |||
| Protection type: Current limiting, delay shut down o/p voltage, re-power on to recover | |||||
| Over Voltage | 110%~135% | ||||
| Protection type: Shut down o/p voltage, re-power on to recover | |||||
| Over Temp. | TSW1(Power transistor) When temp. >100 °C, shut down o/p voltage, re-power on to recover | ||||
| Environment | Working Temp & Humidity | -10°C~+65°C, 20%~90 %RH | |||
| Storage Temp & Humidity | -20°C~+85°C, 10%~95 %RH | ||||
| Vibration | 10~200Hz, 2G 10min./1cycle, period for 60min, each along X, Y, Z axes | ||||
| Safety | Withstand Voltage | I/P-O/P, I/P-FG:1500VAC | |||
| Isolation Resistance | I/P-O/P, I/P-FG, >100MΩ/ 500VDC | ||||
| Standards | Safety Standard | Design UL1950,CSA22.2,IEC60950 | |||
| EMC Standard | Design refer to FCC Part 15 Class A | ||||
| Others | Weight | 2.3Kg; | |||
| Packing | 8pcs/24.0kg/CARTON |
A contactor is built for switching power circuits repeatedly at high current, often with motor duty ratings (AC-3) and arc-suppressing chambers. A relay switches control signals at low current. In practice: contactor for the motor, relay in the control circuit that drives the contactor coil.
Use the motor's full-load current, apply the AC-3 rating for the operating voltage, and allow for the number of starts per hour. As a rule of thumb, the contactor's AC-3 rating should be at least equal to the motor FLC, then step up one frame if the duty is heavy.
Coil voltages are specified per order. Send the model number, coil voltage and frequency you require and we will confirm availability and lead time.
Base models come with the standard auxiliary contact configuration for that frame. Add-on auxiliary blocks and mechanical interlocks can be quoted with the contactor.