The Hdr-60 DIN Rail Power Supply DC for Industrial is part of the ELEHPD HDR-Series range. Hdr-60 DIN Rail Power Supply DC for Industrial from the ELEHPD HDR-Series range. ELEHPD manufactures and exports low voltage electrical products from Yueqing, Zhejiang, China, supplying distributors, panel builders, M&E contractors and OEM buyers worldwide.
Full catalogue description: Hdr-60 DIN Rail Power Supply 60W 24V DC 12V for Industrial Control System
| Model | HDR-60-5 | HDR-60-12 | HDR-60-15 | HDR-60-24 | HDR-60-48 |
| DC Voltage | 5V | 12V | 15V | 24V | 48V |
| Rated Current | 6.5A | 4.5A | 4A | 2.5A | 1.25A |
| Current Range | 0 ~ 6.5A | 0 ~ 4.5A | 0 ~ 4A | 0 ~ 2.5A | 0 ~ 1.25A |
| Rated Power | 32.5W | 54W | 60W | 60W | 60W |
| Ripple & Noise (max.) | 80mVp-p | 120mVp-p | 120mVp-p | 150mVp-p | 240mVp-p |
| Voltage Adj. Range | 5.0 ~ 5.5V | 10.8 ~ 13.8V | 13.5 ~ 18V | 21.6 ~ 29V | 43.2 ~ 55.2V |
| Voltage Tolerance | ±2.0% | ±1.0% | ±1.0% | ±1.0% | ±1.0% |
| Line Regulation | ±1.0% | ±1.0% | ±1.0% | ±1.0% | ±1.0% |
| Load Regulation | ±1.0% | ±1.0% | ±1.0% | ±1.0% | ±1.0% |
| Setup, Rise Time | 500ms, 50ms/230VAC 500ms, 50ms/115VAC at full load | ||||
| Hold Up Time | 30ms/230VAC 12ms/115VAC at full load | ||||
| Voltage Range | 85 ~ 264VAC (277VAC operational ) 120 ~ 370VDC (390VDC operational ) | ||||
| Frequency Range | 47 ~ 63Hz | ||||
| Efficiency | 85% | 88% | 89% | 90% | 91% |
| AC Current | 1.2A/115VAC 0.8A/230VAC | ||||
| Inrush Current | COLD START 30A/115VAC 60A/230VAC | ||||
| | 105 ~ 160% rated output power | ||||
| Hiccup mode when output voltage <50%, recovers automatically after fault condition is removed | |||||
| Constant current limiting within 50% ~100% rated output voltage, recovers automatically after fault condition is removed | |||||
| Over Voltage | 5.75 ~ 6.75V | 14.2 ~ 16.2V | 18.8 ~ 22.5V | 30 ~ 36V | 56.5 ~ 64.8V |
| Protection type : Shut down o/p voltage, re-power on to recover | |||||
| Working Temp. | -30 ~ +70ºC (Refer to "Derating Curve") | ||||
| Working Humidity | 20 ~ 90% RH non-condensing | ||||
| Storage Temp., Humidity | -40 ~ +85ºC, 10 ~ 95% RH non-condensing | ||||
| Temp. Coefficient | ±0.03%/ºC (0 ~ 50ºC) RH non-condensing | ||||
| Vibration | 10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6 | ||||
| Operating Altitude | 2000 meters | ||||
| Safety Standards | UL62368-1, UL508, TUV EN61558-2-16, IEC62368-1, EAC TP TC 004, BSMI CNS14336-1 approved; Design refer to EN62368-1 | ||||
| Withstand Voltage | I/P-O/P:4KVAC | ||||
| Isolation Resistance | I/P-O/P:100M Ohms / 500VDC / 25ºC/ 70% RH | ||||
| MTBF | 927.6K hrs min. MIL-HDBK-217F (25ºC) | ||||
| Dimension | 52.5*90*54.5mm (W*H*D) |
A contactor is built for switching power circuits repeatedly at high current, often with motor duty ratings (AC-3) and arc-suppressing chambers. A relay switches control signals at low current. In practice: contactor for the motor, relay in the control circuit that drives the contactor coil.
Use the motor's full-load current, apply the AC-3 rating for the operating voltage, and allow for the number of starts per hour. As a rule of thumb, the contactor's AC-3 rating should be at least equal to the motor FLC, then step up one frame if the duty is heavy.
Coil voltages are specified per order. Send the model number, coil voltage and frequency you require and we will confirm availability and lead time.
Base models come with the standard auxiliary contact configuration for that frame. Add-on auxiliary blocks and mechanical interlocks can be quoted with the contactor.