How to choose an AC contactor: utilization categories AC-1/AC-3/AC-4, coil voltage, and why the same contactor has different ratings.
A contactor is rated by current, but the number on the label only means something once you state the duty. The same 25 A contactor might be allowed 25 A for a heater and only 9 A for a directly started motor — the utilization category is the difference.
| Category | Load | Typical use |
|---|---|---|
| AC-1 | Resistive, non-inductive | Heaters, ovens, lighting banks |
| AC-3 | Squirrel-cage motor, start + run | Pumps, fans, conveyors (most common) |
| AC-4 | Motor, frequent start/plug reverse | Cranes, hoists, presses |
AC-3 and AC-4 make and break motor current including the starting surge, so their allowed current is far lower than AC-1 for the same contactor. Picking AC-1 data for a motor under-rates the device and welds the contacts.
The coil must match the control supply: 24 V DC, 110 V AC, 230 V AC are common. A 230 V coil on a 24 V PLC output will not pull in; a 24 V coil on 230 V burns out. Keep the coil supply derived from the same source the PLC or pushbuttons use.