Global Trade · Reliable Power Solutions E-mail: [email protected]

RCD vs RCBO vs RCCB: Residual Current Protection Guide

RCD, RCBO and RCCB explained for buyers: Type AC vs Type A, 30 mA vs 100 mA/300 mA, pole configurations, and when to specify an RCBO instead of an RCD plus MCB.

Residual-current devices are the protection that trips on current leaking to earth rather than on overcurrent, and they are the part most often specified wrong because the names — RCD, RCBO, RCCB, ELCB, GFCI — overlap while the standards use different letters. This guide sets out what each one does, the choices that actually change the part number, and what to put on a purchase order.

1. The family at a glance

All of these devices compare the current leaving a circuit with the current returning. If the difference — the "residual current" — exceeds the rating, they open. What differs is the sensing type, whether they also break overcurrent, and how many poles they switch.

DeviceBreaks overcurrent?Typical use
RCCB / RCD (residual-current only)NoPure earth-leakage protection, paired with an MCB or fuse
RCBO (residual + overcurrent)YesCombined earth-leakage and overcurrent in one module-wide device
ELCB (older voltage-operated)NoLegacy installations; largely superseded by RCCB
GFCI (North American term)VariesUS/Canada receptacle or breaker form

2. RCD/RCCB versus RCBO — the practical difference

An RCCB (often just called an RCD) only senses earth leakage. It must sit behind an MCB or fuse that handles overload and short circuit, and it needs its own pole(s). An RCBO does both jobs in a single, usually one- or two-module-wide device. For a new consumer unit or panel where space and per-circuit isolation matter, RCBO per circuit is common; for a main incomer or a retrofit where you only want to add earth-leakage protection to an existing board, an RCCB ahead of the existing breakers is simpler.

The trade-off is cost and selectivity: a single RCCB protects many circuits, but any leakage on any of them trips the whole group; RCBOs localise the fault to one circuit. Specify RCBO when you cannot tolerate a whole-board trip, and RCCB when you want one device protecting a group and accept the group trip.

3. Type AC, Type A and Type F — what the "type" means

The type states which leakage waveforms the device will detect.

TypeDetectsWhere required
AC50/60 Hz sinusoidal AC leakage onlyLegacy resistive loads; increasingly not accepted
AAC plus pulsating DC (half-wave rectified)Modern equipment, drives, LED drivers, EV, appliances
FA plus higher-frequency AC and mixed frequenciesVFDs, dimmers, complex electronic loads

For almost any panel feeding modern electronics, Type A is the minimum to specify; Type AC will miss the DC-component leakage that today's drives and power supplies produce, so the protection may not operate as expected. Confirm Type A unless you have a documented reason for AC, and use Type F where variable-frequency drives or dimmers are present.

4. The rating: 30 mA, 100 mA or 300 mA

The rating is the residual current at which the device trips. 30 mA is the value for personal protection — the threshold below which a shock is unlikely to be fatal, and the usual requirement for sockets and final circuits in dwellings, bathrooms, outdoor and construction supplies. 100 mA and 300 mA are for fire protection and for the upstream device in a selective (time-delayed) arrangement, where a downstream 30 mA device must trip first.

Two rules: do not put 30 mA where a standing leak (large IT loads, long cable runs) will cause nuisance tripping — use 100 mA or 300 mA for that group and keep 30 mA for the final circuits; and where two devices are in series, the upstream one must be time-delayed (S-type) so the downstream one clears first.

5. Pole configuration and the supply system

Residual-current devices come in 2-pole (single-phase, switches line and neutral) and 4-pole (three-phase plus neutral). For single-phase supplies use 1P+N or 2P; for three-phase use 3P+N or 4P. Switching the neutral matters: if neutral is not interrupted, a fault can leave a live-neutral loop that defeats the protection. State the pole count on the order, and confirm the device is approved for the supply system (TN-C-S, TT, TN-S) you are installing into.

6. What to put on the purchase order

  1. Device type: RCCB, RCBO or GFCI, and whether it replaces an existing ELCB.
  2. Sensing type: Type A unless a documented exception, Type F for VFD/dimmer loads.
  3. Rating: 30 mA for final circuits and personal protection; 100/300 mA for fire or upstream selective protection.
  4. Pole configuration: 1P+N/2P for single-phase, 3P+N/4P for three-phase.
  5. Breaking capacity and the MCB frame it must coordinate with (for an RCCB, or integrated for an RCBO).
  6. Selectivity: time-delayed (S) upstream device where two are in series.
  7. Approvals for the destination market (CE/BS/UL as applicable).

ELEHPD supplies RCBO, RCCB/RCD, ELCB and GFCI devices in Type A and Type AC, 30/100/300 mA, 1P+N through 4P, with the matching MCBs and distribution boards for a complete earth-leakage protection scheme.

Related ELEHPD products

Browse every ELEHPD model

Related product categories

Talk to us about your specification

Send the ratings, dimensions and quantities you are working to and we will confirm the closest match from the ELEHPD catalogue, the compliance documents available for it and the lead time. OEM branding, private model numbering and buyer-specific cartons are available on qualified volumes.

Request a quotation See the catalogue