Miniature Circuit Breaker (MCB) Selection Guide: Curves, kA and Poles

How to choose a miniature circuit breaker: tripping curve B/C/D, rated current, breaking capacity (kA), number of poles, and how to size an MCB for a lighting or motor circuit to IEC 60898.

A miniature circuit breaker (MCB) is the default overcurrent protector in every low-voltage distribution board: it carries the load continuously and trips automatically on overload or short circuit, then resets by hand instead of being discarded like a fuse. For panel builders, distributors and importers, the catalogue number is fixed by four choices — curve, rated current, breaking capacity and pole count — and getting them wrong means either nuisance trips or a board that cannot survive a fault. This guide walks the choices.

1. Tripping curve: B, C or D

The letter is the magnetic trip threshold in multiples of rated current (In):

CurveMagnetic tripUse
B3–5 × InResistive loads, lighting, low inrush — homes and offices
C5–10 × InGeneral mix of lighting + sockets; the common commercial default
D10–20 × InTransformers, motors, capacitive loads with high inrush

Curve C suits most panels; pick D for anything with a hard start (motor, welding transformer, large LED driver) and B only where inrush is genuinely tiny. A D-curve on a plain lighting circuit will not nuisance-trip but also masks a fault longer than it should.

2. Rated current (In)

In is the current the MCB carries forever without tripping. Size it from the circuit load with headroom, not to the cable's limit:

3. Breaking capacity (kA)

This is the fault current the MCB can safely interrupt once. A 6 kA device is fine for a final sub-circuit fed from a limiting upstream breaker, but the main incomer or a board close to a transformer may see tens of kA, where you need 10 kA or higher. Match the kA rating to the prospective short-circuit current at that point in the board, confirmed by the upstream protective device.

4. Number of poles

In TN-C-S and TT systems the neutral-handling rule varies; size poles to the circuit topology and local wiring code, not habit.

5. Standards and compatibility

Domestic and similar boards use IEC 60898 (rated up to 125 A, 440 V); industrial assemblies reference IEC 60947-2. Confirm the MCB matches the busbar and DIN rail of the board you are building, the trip characteristics your code expects, and any required markings (CE, ROHS). Mixing a 60898 device into a 60947-2 assembly changes the standards basis of the whole board.

6. What to put on the RFQ

  1. Curve (B/C/D) from the load inrush profile.
  2. Rated current In from the circuit load with margin.
  3. Breaking capacity (kA) from the prospective fault level at that point.
  4. Pole count from the circuit topology.
  5. Rated voltage and standard (IEC 60898 or 60947-2).
  6. Any required approvals and the rail/busbar format of the target board.

ELEHPD manufactures DIN-rail MCBs in curves B, C and D, from 1 A to 63 A, in 6 kA and 10 kA breaking capacities, 1P–4P, built to IEC 60898 and made to drop straight onto standard 35 mm rails alongside RCCBs, contactors and din-rail power supplies.

Related ELEHPD products

Browse every ELEHPD model

Related product categories

Talk to us about your specification

Send the ratings, dimensions and quantities you are working to and we will confirm the closest match from the ELEHPD catalogue, the compliance documents available for it and the lead time. OEM branding, private model numbering and buyer-specific cartons are available on qualified volumes.

Request a quotation See the catalogue

Available Languages