Float Switches & Level Control · Global Supply E-mail: [email protected]

Float Switch Cable Length & Voltage Drop Calculator

A free, no-sign-up reference for installers, panel builders and procurement engineers sizing a cable float switch run. It calculates voltage drop, the maximum one-way cable length for your allowed drop, and flags contact-rating limits. The tool and its dataset are reusable under CC BY 4.0 — embedding and citation snippets are below.

1. Calculator

Cable voltage-drop calculator

Results update as you type. No data leaves this page.
Copper resistivity at this temperature
—
Voltage drop at this length
—
Drop as share of supply
—
Allowed drop (your setting)
—
Maximum one-way cable length
—
Result at this length
—

ΔU = 2 × ρ(T) × L × I / A   |    Lmax = (V × allowed%) × A / (2 × ρ(T) × I)   |    ρ(T) = 0.0175 × [1 + 0.00393 × (T − 20)] Ω·mm²/m

L = one-way cable length in metres, A = conductor cross-section in mm², I = switched current, V = supply voltage, T = conductor temperature. The factor 2 accounts for the out-and-back loop. Copper values at 20 °C; the temperature coefficient is 0.00393 /°C.

2. What the numbers mean

Float switches usually carry a small control current — a contactor coil, a PLC input or an alarm — so voltage drop rarely limits a 2–15 m factory-fitted cable. The calculation matters when the run is extended across a pump station, when several floats share a long multicore, or when a low-voltage control circuit is used. If the load current is a motor current, the float should never be switching it directly: put a contactor in the panel.

Values on this page are a screening aid, not a certified design. They come from the published UKY catalogue data, not from a test report. Verify the final installation against local wiring rules.

3. Open dataset (CSV, CC BY 4.0)

Five stock UKY cable lengths with the catalogue ratings, one row per model, ready to import into a spreadsheet, a comparison table or a teaching example. Download the CSV dataset.

ModelCable (m)Rated / isolationContacts (A)ProtectionRated / working (°C)CoresSource
90012250 / 380 V AC16 (8) / 10 (8) / 10 (4)IP68CS70 / 0–803datasheet
90023250 / 380 V AC16 (8) / 10 (8) / 10 (4)IP68CS70 / 0–803datasheet
90035250 / 380 V AC16 (8) / 10 (8) / 10 (4)IP68CS70 / 0–803datasheet
900410250 / 380 V AC16 (8) / 10 (8) / 10 (4)IP68CS70 / 0–803datasheet
900515250 / 380 V AC16 (8) / 10 (8) / 10 (4)IP68CS70 / 0–803datasheet

4. Wiring concept

Cable float switch control concept A tilting float operates a changeover microswitch. The switch feeds a contactor coil, which starts or stops the pump motor. Core colours are intentionally not assigned. Tank / sump tilting float 3-core cable Changeover switch COM → NO / NC pump-up or pump-down Contactor coil inside control panel Pump motor start / stop Concept only. Core-to-NO/NC assignment varies by model and batch: verify against the wiring diagram supplied with your part number. Mains wiring by a qualified electrician.

The float tilts with the level and operate a changeover microswitch. One 3-core (black / blue / brown) unit covers both pump-up and pump-down duty by reversing two cores; a second float gives an independent high-level alarm or dry-run protection. We do not publish a fixed core-colour to NO/NC mapping because it varies by model and batch — always check the wiring diagram supplied with your part number.

5. Selection checklist

6. Cite or embed this page

This page, the calculator and the CSV are published under CC BY 4.0. Use them freely in articles, datasheets, course material or internal tools — the only condition is a visible attribution link back to this page. That link is how we keep the resource free.

HTML citation

<a href="https://www.elehpd.com/float-switch-cable-calculator">ELEHPD — Float Switch Cable Length &amp; Voltage Drop Calculator</a> (CC BY 4.0)

Markdown

[ELEHPD — Float Switch Cable Length & Voltage Drop Calculator](https://www.elehpd.com/float-switch-cable-calculator) (CC BY 4.0)

BibTeX

@misc{elehpd2026cable, title = {Float Switch Cable Length and Voltage Drop Calculator}, author = {{ELEHPD}}, year = {2026}, url = {https://www.elehpd.com/float-switch-cable-calculator}, note = {Free engineering calculator and open CSV dataset, CC BY 4.0} }

Embed the calculator (with attribution)

<iframe src="https://www.elehpd.com/tools/voltage-drop-calculator?ref=embed" width="100%" height="520" loading="lazy" title="Float switch cable voltage drop calculator by ELEHPD" style="border:1px solid #d8dee6;border-radius:8px"></iframe> <p style="font:12px sans-serif;color:#5b6875">Calculator by <a href="https://www.elehpd.com/float-switch-cable-calculator">ELEHPD</a> (CC BY 4.0)</p>

Prefer the raw data? The CSV is served as a static file with a stable URL: https://www.elehpd.com/data/float-switch-cable-dataset.csv.

7. Questions engineers ask

Is this calculator a substitute for an electrical design check?

No. It uses a simplified resistive model for a copper two-way circuit. It ignores reactance, conductor heating, motor inrush, harmonics, earthing and local wiring rules. Use it as a first-pass screening tool only; a qualified electrician must confirm the final installation against the applicable national standard.

Which core colour is normally open and which is normally closed?

We deliberately do not publish a universal colour mapping. Core assignment varies by model and production batch. The UKY 3-core black / blue / brown cable supports both pump-up (fill) and pump-down (empty) duty by reversing two cores, but you must verify the actual assignment against the wiring diagram supplied with your part number before energising the circuit.

Can I use this calculator and the dataset on my own site?

Yes. Both are published under CC BY 4.0. You may embed the calculator or reproduce the CSV, including in commercial or teaching material, as long as you keep the visible attribution link to this page. Copy-ready HTML, Markdown, BibTeX and iframe snippets are provided below.

Are standard models Ex rated or approved for drinking-water contact?

No. Standard UKY models are not Ex / intrinsically safe. We do not claim WaterMark, AS/NZS 4020, EAC/GOST or Vietnamese CR certification here. Whether a finished assembly needs a local conformity mark depends on its HS code and regulation and must be determined by the importer or panel builder. Available technical files are supplied on request.

8. Need a datasheet or a quotation?

Send the cable length, contact rating / supply voltage and approximate quantity and we will return the datasheet, wiring diagram and a factory-direct price. Spares and documentation ship from the factory; we do not maintain local repair centres or spare-parts warehouses in the destination market.

Request datasheet / quote →